3. Cabling
3-102
TI 33Q01J10-01E
ER Bus Converting Adapter
The converting adapter is required when connecting 10BASE-2 and 10BASE-5 cable.
SEE
ALSO
For more information about the converting adapter, see the following:
“● Control Bus Adapter” in “3.8 Connecting Bus Cable”
10BASE-5 Cable
When 10BASE-5 cable is used, a grounding unit (YCB117) should be used for grounding.
For one segment (a communication range of bus connection that no repeater is used), one
point per bus needs to be grounded.
SEE
ALSO
For more information about the grounding unit, see the following:
“● V net cable (10BASE-5)” in “3.8 Connecting Bus Cable”
Feb. 1, 2009-00