3. Cabling
3-38
TI 33Q01J10-01E
FIO Signal Cabling
IMPORTANT
The signal cable for the top node unit must be wired at the innermost part in the field control area
as the figure shows.
When fixing cables to a clamp, allow enough space so that the cards can be maintained.
Bind the bottom cables to the clamp bar on the channel base.
Push in the signal cables for the top node unit as far as they will go.
F030514.ai
Front
Node unit
(1)
(2)
(3)
(4)
(5)
(1): Signal Cables for
the top node unit
(5): Signal Cables for
the Bottom node unit
Cable binding
bar
Figure Signal Cabling
FIO with KS Cable Interface Adapter Cabling
Make a blunt curb for wiring when the dedicated cable is connected to FIO.
Lay the cables in front side of a separator on cable tray.
F030515.ai
90 mm
Separator
Cable tray
To reserve the ventilation for I/O module,
the signal cable should not exceed the
separator at the center of cable tray.
Figure FIO with KS Cable Interface Adapter Cabling
Sep. 30, 2008-00