The calibration operation allows the measurement of ratio of the welding current
command and the actual welding current value based on the welding current value of
2 seconds to 6 seconds after welding start.
The “Record” lamp blinks when the calibration measurement is confirmed
If the welding time is less than 6 seconds, the “Record” lamp does not blink after the
welding. Make the weld length longer and perform the welding current calibration
again.
(5)
Confirming the Result of Current Calibration 2
Keep pressing the “R” button to confirm the result of current calibration 2
V
A
Wire m/min
Type
The display of “V”: Displays the execution of calibration 2
The display of “A”: Displays the welding current command value at the execution of
calibration 2
(The value is registered in C parameter.)
The display of “Wire”: Displays the measurement result of calibration 2
(The result is registered in the parameter P63.)
(Welding current command value/actual welding current value
×
100%)
The example display shown above indicates:
The result of calibration 2: 95%
The welding current command: 250A
(6)
Saving the Conditions of Calibration Result
After confirming the measurement result, keep pressing the “Record” button for 3
seconds or more to save the result.
(7)
Returning to the Usual Welding Mode
Perform one of the followings to move to the usual welding mode.
- Press “P.R.M.Select” button; or
- Turn OFF the welder once and turn it ON again.
The welding after the welding current calibration is performed by the wire feeding
speed command which is calculated from the welding current calibration result.