YASKAWA
TOMPYEULA7002A LA700 Series Installation and Operation Instruction
361
Drive Model
Residual Current Monitor/Residual Current Device (RCM/RCD)
Without AC or DC Reactor
With AC or DC Reactor
Model
Rated Current (A)
Model
Rated Current (A)
2041
NV125-SV
60
NV125-SV
50
2059
NV125-SV
75
NV125-SV
75
2075
NV250-SV
125
NV125-SV
100
2094
NV250-SV
150
NV250-SV
125
2110
-
NV250-SV
150
2144
-
NV250-SV
175
2181
-
NV250-SV
225
2225
-
NV400-SW
250
2269
-
NV400-SW
300
2354
-
NV400-SW
400
2432
-
NV630-SW
500
2519
-
NV630-SW
600
*1
Drive models 2110 to 2519 have a built-in DC reactor for power factor improvement as standard.
Table 10.12 Three-Phase 400 V Class
Drive Model
Residual Current Monitor/Residual Current Device (RCM/RCD)
Without AC or DC Reactor
With AC or DC Reactor
Model
Rated Current (A)
Model
Rated Current (A)
4012
NV32-SV
20
NV32-SV
15
4019
NV32-SV
30
NV32-SV
20
4023
NV32-SV
30
NV32-SV
30
4030
NV63-SV
50
NV63-SV
40
4039
NV125-SV
60
NV63-SV
50
4049
NV125-SV
75
NV125-SV
60
4056
-
NV125-SV
75
4075
-
NV125-SV
100
4094
-
NV250-SV
125
4114
-
NV250-SV
150
4140
-
NV250-SV
175
4188
-
NV250-SV
225
4225
-
NV400-SW
250
4270
-
NV400-SW
300
4325
-
NV400-SW
350
4380
-
NV400-SW
400
*1
Drive models 4056 to 4380 have a built-in DC reactor for power factor improvement as standard.
◆
CE Standards Compliance for DC Power Supply Input
To comply with CE Standards, install a fuse for the DC power supply input.
shows a wiring example for a DC power supply that has two drives connected in parallel.