![YASKAWA JEPMC-MP2300S-E Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/yaskawa/jepmc-mp2300s-e/jepmc-mp2300s-e_user-manual_907071065.webp)
2.2 Basic Module
2.2.5 Built-in SVB Module
2-41
2
Specifications and Functions
Transmission Bytes, Communication Cycle, Number of Retries to Slaves, Number of Slaves
Transmission bytes, communication cycle, number of retries to slaves, and number of slaves at execution of self-con-
figuration will be automatically set according to conditions including communication type, station type (Master or
Slave), and the largest slave station number (the largest number among the detected slave station numbers).
<For Master Station>
SigmaWin
(Hidden for
MECHATROLINK
-I)
For MECHATROLINK-II communications, displays
whether or not to use S for communication via
MECHATROLINK-II adapter such as JUSP-NP115.
Select either
use
or
not use
.
Number of
Retry to Slaves
(Hidden for
MECHATROLINK
-I)
Displays the maximum number of slave stations to which
the Master can retry transmission in one transmission
cycle when the Master has not received a normal
response from a slave.
Only for Master station. Set a number between
0 and 7. Cannot set for Slaves.
Number of Slaves
Displays the number of slave stations that can be con-
nected.
The number of slave stations that can be connected is
determined by communication type, communication
cycle, S use/not use, and number of retry to
slaves.
Cannot be set.
Slave Synchro-
nous Function
When using a built-in SVB as a slave station, select
whether to synchronize with a master station.
Select either
Enable
or
Disable
.
For more information about the process, refer
to
Chapter 7 Slave CPU Synchronous Func-
tion
.
Item
MECHATROLINK-
II
(32-byte mode)
MECHATROLINK-
II
(17-byte mode)
MECHATRO-
LINK-
I
Largest Slave
Station Number
1 to 8
9
10 to 16
17 to 21
1 to 14
15
Transmission
Byte
31 bytes
16 bytes
−
Communication
Cycle
1 ms
1 ms
2 ms
2 ms
1 ms
1 ms
2 ms
Number of
Retry to Slaves
1
0
5
21
(The largest slave
station number)
1
0
14
Number of
Slaves
8
9
16
The largest slave
station number
14
15
14
(cont’d)
Item
Display during Self-configuration
Options and Precautions on Settings
Содержание JEPMC-MP2300S-E
Страница 14: ...MEMO ...
Страница 24: ...MEMO ...
Страница 114: ...MEMO ...
Страница 132: ...MEMO ...
Страница 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Страница 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Страница 190: ...MEMO ...
Страница 280: ...MEMO ...
Страница 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Страница 302: ...7 3 Operation 7 3 5 How to Determine Input Error 7 22 Application Example Continued on the next page ...
Страница 306: ...7 3 Operation 7 3 6 Management to Resume Slave CPU Synchronization 7 26 Application Example Continued on the next page ...
Страница 310: ...MEMO ...