7.3 Operation
7.3.4 How to Use Scan Counter
7-17
7
Slave CPU Synchronous Function
7.3.4 How to Use Scan Counter
A scan counter enables the reception device to check that data is updated by the transmission device.
It also allows the master and slave to confirm each other’s proper working order.
Use of the scan counter is optional, and there is no problem if you choose not to use it.
An example follows. In this example, H scan cycles of both master and slave sides are assumed to have the same set-
ting.
( 1 ) Checking the Master Status Using a Slave Side Application
Master processing
A master side application is increased the setting value by one for the start word of an output register assigned to the
MP2300S/SVB.
Slave processing
A slave side application checks that the scan counter value is increased by one from the previous value +1. As the scan
counter is one byte of data, it only checks the lower byte.
If not updated normally, it determines that a problem has occurred with the master.
( 2 ) Checking a Slave Status Using a Master Side Application
Master processing
A master side application checks that a scan counter value is increased by one from the previous value. As the scan
counter is one byte of data, it only checks the lower byte.
If not updated normally, it determines that a problem has occurred with the slave.
Slave processing
A slave side application is increased the setting value by one for the start word of an output register mapped to SVB.
Note: In this example, H scan cycles of both master and slave sides have the same setting.
When they have a different scan cycle setting, they must be updated and checked accordingly.
OW
IW
OW
+1
IW
+1
Master
Slave
Updates each scan
with the application
Output register
Input register
Scan
counter
Scan
counter
Checks that the counter is updated.
If not updated properly, determines that
the master side operation is abnormal.
IW
OW
IW
+1
OW
+1
Master
Slave
Input register
Output register
Scan
counter
Scan
counter
Checks that the counter is updated.
If not updated properly, determines that
the slave side operation is abnormal.
Updates each scan
with the application
Содержание JEPMC-MP2300S-E
Страница 14: ...MEMO ...
Страница 24: ...MEMO ...
Страница 114: ...MEMO ...
Страница 132: ...MEMO ...
Страница 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Страница 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Страница 190: ...MEMO ...
Страница 280: ...MEMO ...
Страница 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Страница 302: ...7 3 Operation 7 3 5 How to Determine Input Error 7 22 Application Example Continued on the next page ...
Страница 306: ...7 3 Operation 7 3 6 Management to Resume Slave CPU Synchronization 7 26 Application Example Continued on the next page ...
Страница 310: ...MEMO ...