![YASKAWA JEPMC-MP2300S-E Скачать руководство пользователя страница 422](http://html.mh-extra.com/html/yaskawa/jepmc-mp2300s-e/jepmc-mp2300s-e_user-manual_907071422.webp)
A-68
Example: When reading coil state with offset:
The various setting values and their relationships with the data of the remote device are as follows, when transmitting
“reading coil state” with offset in MEMOBUS protocol:
• Description of the MSG-SND function in ladder program
• Parameter list setting of the MSG-SND function
Note: IN: Input, OUT: Output, SYS: For system use
Table G.19 Parameter List Setting
Register Num-
ber
Setting
Value
Parameter Num-
ber
IN/OUT
Remarks
DW00000
–
PARAM00
OUT
Process result
DW00001
–
PARAM01
OUT
Status
DW00002
00001
PARAM02
IN
Connection number=1
DW00003
–
PARAM03
IN
Option (setting unnecessary)
DW00004
00001
PARAM04
IN
Function code=1 (reads coil state)
DW00005
08192
PARAM05
IN
Data address=8192 bits (512 words)
DW00006
00100
PARAM06
IN
Data size=100
DW00007
00001
PARAM07
IN
Remote CPU number=1
DW00008
01000
PARAM08
IN
Coil offset=1000 words
DW00009
00000
PARAM09
IN
Input relay offset=0 word
DW00010
00000
PARAM10
IN
Input register offset=0 word
DW00011
00000
PARAM11
IN
Holding register offset=0 word
DW00012
–
PARAM12
SYS
Reserved (zero clear at startup)
DW00013
–
PARAM13
SYS
Reserved
DW00014
–
PARAM14
SYS
Reserved
DW00015
–
PARAM15
SYS
Reserved
DW00016
–
PARAM16
SYS
Reserved
Execute
Communication device = 218IFA
Protocol = MEMOBUS
Circuit number = 1
Communication buffer channel number = 1
Parameter list start address
(use DW00000 to DW00016)
Abort
Dev-Typ
Pro-Typ
Cir-No
Ch-No
Param
MSG-SND
Busy
Complete
Error
DB000201
DB000202
00016
00001
00001
DA00000
00001
DB000210
DB000211
DB000212
Содержание JEPMC-MP2300S-E
Страница 14: ...MEMO ...
Страница 24: ...MEMO ...
Страница 114: ...MEMO ...
Страница 132: ...MEMO ...
Страница 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Страница 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Страница 190: ...MEMO ...
Страница 280: ...MEMO ...
Страница 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Страница 302: ...7 3 Operation 7 3 5 How to Determine Input Error 7 22 Application Example Continued on the next page ...
Страница 306: ...7 3 Operation 7 3 6 Management to Resume Slave CPU Synchronization 7 26 Application Example Continued on the next page ...
Страница 310: ...MEMO ...