![YASKAWA JEPMC-MP2300S-E Скачать руководство пользователя страница 450](http://html.mh-extra.com/html/yaskawa/jepmc-mp2300s-e/jepmc-mp2300s-e_user-manual_907071450.webp)
A-96
[ d ] PARAMETER (parameter)
When RESULT (process result) = 4 (FMT_NG: parameter format error), an error code in the following table is output.
Otherwise, the connection number is output.
( 4 ) Connection Number (PARAM02)
Refer to
G.2.4 ( 4 ) Connection Number (PARAM02)
on page A-80.
( 5 ) Data Size (PARAM06)
A data size requested from the transmission side is output.
In case of non-procedure 1, the number of words is output.
In case of non-procedure 2, the number of bytes is output.
( 6 ) Register Offset (PARAM12)
Specify an offset address for the reception side data address.
The address for the reception side will be displaced by the number of words designated by the offset.
Note: 1. For more information, refer to
G.2.8 Relationship between Data Address, Data Size, and Offset for
MSG-RCV Function
on page A-98.
2. The offset cannot be a negative value.
In case of non-procedure, received continuous data is stored in the M register. Setting the register offset enables you to
specify a start address of the M register as a storage area.
Example: When specifying MW01000 for the start address of the M register for storing received data:
PARAM12=1000
RESULT (process result)
Code (Hex)
Meaning
When RESULT (process re-
sult) = 4
(FMT_NG: parameter for-
mat error)
00
No error
01
Connection number is out of range
02
Time error while monitoring to receive MEMOBUS response
(for MEMOBUS protocol)
03
Error in setting retransmit count
04
Error in setting cyclic area
05
CPU number error
06
Data address error
07
Data size error
08
Function code error (for MEMOBUS protocol)
Others
xx
Connection number
Содержание JEPMC-MP2300S-E
Страница 14: ...MEMO ...
Страница 24: ...MEMO ...
Страница 114: ...MEMO ...
Страница 132: ...MEMO ...
Страница 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Страница 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Страница 190: ...MEMO ...
Страница 280: ...MEMO ...
Страница 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Страница 302: ...7 3 Operation 7 3 5 How to Determine Input Error 7 22 Application Example Continued on the next page ...
Страница 306: ...7 3 Operation 7 3 6 Management to Resume Slave CPU Synchronization 7 26 Application Example Continued on the next page ...
Страница 310: ...MEMO ...