A-87
A
Appendices
( 10 ) Offset (PARAM08, PARAM09, PARAM10, PARAM11)
Specify an offset address for the reception side data address.
The address for the reception side will be displaced by the number of words designated by the offset.
Note: 1. For more information, refer to
G.2.8 Relationship between Data Address, Data Size, and Offset for
MSG-RCV Function
on page A-98.
2. The offset cannot be a negative value.
The offset parameter is prepared for each target data type.
The following table lists the offset parameters.
The valid offset parameter may differ according to the function code.
The following table lists the valid parameters for the function codes.
Table G.25 Offset Parameter List
Parameter
Contents
Description
PARAM08
Coil offset
Sets the coil's offset word address.
PARAM09
Input relay offset
Sets the offset word address of an input relay.
PARAM10
Input register offset
Sets the offset word address of an input register.
PARAM11
Holding register offset
Sets the offset word address of a holding register.
Table G.26 Valid Parameter List for Offset of Each Function Code
Function Code
Function
Valid Offset Parameter
01H
Reads coil state
PARAM08
02H
Reads input relay state
PARAM09
03H
Reads holding register content
PARAM11
04H
Reads input register content
PARAM10
05H
Changes single coil state
PARAM08
06H
Writes to single holding register
PARAM11
09H
Reads holding register content (extended)
PARAM11
0AH
Reads input register content (extended)
PARAM10
0BH
Writes to holding register (extended)
PARAM11
0EH
Discontinuously writes to holding register (extended)
PARAM11
0FH
Changes multiple coil states
PARAM08
10H
Writes to multiple holding registers
PARAM11
31H
Writes to fixed buffer
PARAM11
32H
Reads the random access buffer
Invalid
33H
Writes to the random access buffer
PARAM11
Содержание JEPMC-MP2300S-E
Страница 14: ...MEMO ...
Страница 24: ...MEMO ...
Страница 114: ...MEMO ...
Страница 132: ...MEMO ...
Страница 154: ...5 2 User Programs 5 2 2 Motion Programs 5 22 2 Example using a ladder program ...
Страница 156: ...5 2 User Programs 5 2 2 Motion Programs 5 24 2 Example using a ladder program ...
Страница 190: ...MEMO ...
Страница 280: ...MEMO ...
Страница 300: ...7 3 Operation 7 3 5 How to Determine Input Error 7 20 Continued from the previous page ...
Страница 302: ...7 3 Operation 7 3 5 How to Determine Input Error 7 22 Application Example Continued on the next page ...
Страница 306: ...7 3 Operation 7 3 6 Management to Resume Slave CPU Synchronization 7 26 Application Example Continued on the next page ...
Страница 310: ...MEMO ...