No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
E2-04
(0311) Number of Motor Poles Number of Poles
Sets the number of motor poles. Automatically set during
Auto-Tuning.
Default: 2
Min.: 2
Max.: 48
E2-05
(0312)
Motor Line-to-Line
Resistance
Term Resistance
Sets the phase-to-phase motor resistance. Automatically set
during Auto-Tuning.
Min.: 0.000 Ω
Max.: 65.000 Ω
E2-06
(0313)
Motor Leakage
Inductance
Leak Inductance
Sets the voltage drop due to motor leakage inductance as a
percentage of motor rated voltage. Automatically set during
Auto-Tuning.
Min.: 0.0%
Max.: 40.0%
E2-10
(0317)
Motor Iron Loss for
Torque Compensation Motor Iron Loss
Sets the motor iron loss.
Min.: 0 W
Max.: 65535 W
E2-11
(0318) Motor Rated Power
Mtr Rated Power
Sets the motor rated power in kilowatts (1 HP = 0.746 kW).
Automatically set during Auto-Tuning.
Min.: 0.00 kW
Max.: 650.00
kW
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units:
BV0006 to BV0018, 2V0006 to 2V0040, and 4V0002 to 4V0023: 0.01 A units.
2V0056 to 2V0069 and 4V0031 to 4V0038: 0.1 A units.
B.6 E: Motor Parameters