• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the Test Report at 115 °C.
n
E2-06: Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
No.
Parameter Name
Setting Range
Default
E2-06
Motor Leakage Inductance
0.0 to 40.0%
Depending on
o2-04
n
E2-10: Motor Iron Loss for Torque Compensation
This parameter sets the motor iron loss in watts.
No.
Parameter Name
Setting Range
Default
E2-10
Motor Iron Loss for Torque Compensation
0 to 65535 W
Depending on
o2-04
n
E2-11: Motor Rated Power
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto-
Tuning completes successfully, the value entered will automatically be saved to E2-11.
No.
Parameter Name
Setting Range
Default
E2-11
Motor Rated Power
0.00 to 650.00 kW
Depending on
o2-04
5.5 E: Motor Parameters
160
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual