n
P9-25: Highest Node Address
Selects the highest possible node address in the Modbus network.
To yield optimal network performance, set serial communication address H5-01 starting from 01h and then consecutively up
to the last drive and then set the P9-25 parameter to highest used H5-01 address.
No.
Name
Setting Range
Default
P9-25
Highest Node Address
2 to 8
8
n
P9-26: Master Time-out
Sets the minimum amount of time that the follower drives will wait for a message from the master before performing the action
set in P9-27.
No.
Name
Setting Range
Default
P9-26
Master Time-out
1.0 to 10.0 s
4.0 s
n
P9-27: Network Recovery
Sets the follower drive response action when no messages are received from the master for the time set in P9-26.
No.
Name
Setting Range
Default
P9-27
Network Recovery
0 to 3
0
Setting 0: Automatic
Drive will attempt to assume master functionality.
Setting 1: Slave/resume
Drive will continue running when the master is lost, and will wait for a master to come online.
Note:
Drive will keep running in its current operation state which could cause an undesirable condition.
Setting 2: Slave/stop
Drive will stop running when the master is lost, and will wait for a master to come online.
Setting 3: Fault MSL
Fault the drive with an MSL (Master Lost).
n
P9-28: NETSCAN Alarm Time
Sets the amount of time that the follower drives will wait for a message from the master before displaying a NETSCAN alarm.
No.
Name
Setting Range
Default
P9-28
NETSCAN Alarm Time
1.0 to 10.0 s
2.0 s
n
P9-29: Net Start Delay
Sets the time that the drive will wait before selecting and starting the lead drive after the first drive on the network has been
put on AUTO mode.
No.
Name
Setting Range
Default
P9-29
Net Start Delay
0.0 to 60.0 s
2.0 s
n
P9-30: Lag Drive Speed Follower Gain
Sets the gain that will be applied to the speed of the current lead drive when Lag Drive Mode is activated.
No.
Name
Setting Range
Default
P9-30
Lag Drive Speed Follower Gain
0.0 to 300.0%
100.0%
n
P9-31: Lag Drive Speed Follower Bias
Sets the bias that will be applied to the speed of the current lead drive when Lag Drive Mode is activated.
No.
Name
Setting Range
Default
P9-31
Lag Drive Speed Follower Bias
-60.0 to 60.0 Hz
0.0 Hz
5.11 P: Pump
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
243
5
Parameter Details