Table 5.19 Constant Output, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
7
14
200
1.5 3
90
60
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
120
60
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
180
60
Voltage (V)
Frequency (Hz)
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
Setting a Custom V/f Pattern
Setting parameter E1-03 to “F” allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When E1-03 is changed to “F”, the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 1 of the predefined
patterns.
n
V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if E1-03
≤
15 or set up a custom V/
No.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 400.0 Hz
60.0 Hz
E1-05
Maximum Voltage
0.0 to 255.0 V
E1-06
Base Frequency
0.0 to E1-04
60.0 Hz
E1-07
Middle Output Frequency
0.0 to E1-04
3.0 Hz
E1-08
Middle Output Frequency Voltage
0.0 to 255.0 V
E1-09
Minimum Output Frequency
0.0 to E1-04
1.5 Hz
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0 V
E1-11
Middle Output Frequency 2
0.0 to E1-04
0.0 Hz
E1-12
Middle Output Frequency Voltage 2
0.0 to 255.0 V
0.0 V
Base Voltage
0.0 to 255.0 Hz
0.0 V
<1> Values shown are for 200 V class drives; double the value when using 400 V class drives.
<2> When E1-13 is set to 0.0 V, the drive uses the value set in E1-05 to control the voltage.
Output Voltage (V)
Frequency (Hz)
Figure 5.38 V/f Pattern
Note:
1.
The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2.
Setting E1-11 to 0 disables both E1-11 and E1-12 and the above conditions do not apply.
3.
To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
4.
E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned to their
default values.