5.10 o: Operator Related Settings
These parameters concern the various functions and features of the digital operator.
u
o1: Display Settings and Selections
These parameters determine how data is shown on the operator display.
n
o1-01: Drive Mode Unit Monitor Selection
When using an LED operator, pressing the up arrow key on the drive will display the following data: frequency reference →
rotational direction → output frequency → output current → o1-01 selection.
Parameter o1-01 selects the content of the last monitor in this sequence. There is no effect like this on an LCD operator.
No.
Name
Setting Range
Default
o1-01
Drive Mode Unit Monitor Selection
104 to 904
106 (U1-06)
<1> U2-
parameters cannot be selected.
To select a monitor parameter, set the three numeric digits that make up that monitor. This is done by entering the
o
-
oo
part
of U
o
-
oo
.
n
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the drive
is first turned on.
No.
Name
Setting Range
Default
o1-02
User Monitor Selection after Power Up
1 to 5
1
Setting 1: Frequency Reference (U1-01)
Setting 2: Forward/Reverse
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Selected Monitor (set by o1-01)
Setting 5 displays the monitor selected from the U parameter by o1-01.
n
o1-03: Digital Operator Display Selection
Sets the units used to display the frequency reference and output frequency.
Set this parameter to 3 for user-set units before setting parameters o1-10 and o1-11.
No.
Name
Setting Range
Default
o1-03
Digital Operator Display Selection
0 to 3
0
Setting 0: 0.01 Hz Units
Setting 1: 0.01% Units
100% = max output frequency.
Setting 2: r/min Units
Calculated by the max output frequency and the number of motor poles.
Note:
Setting 2 requires entering the number of motor poles to E2-04, E4-04, and E5-04.
Setting 3: User-Set Units (use o1-01 and 01-11)
Set the value used for the maximum frequency reference to o1-10, then set the placement of the decimal point in this number
to o1-11.
For example, to display the maximum output frequency as “100.00”, set o1-10 to 10000 and o1-11 to 2 (i.e., 10000 with two
numbers to the right of the decimal point).
Note:
Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
5.10 o: Operator Related Settings
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
215
5
Parameter Details