Long blink
(50% duty)
Double blin k
Short link
(15% duty)
1 s
2 s
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Figure 4.6 AUTO LED and HAND LED Timing Status
OFF
ON
Blink OFF
Blink
OFF
Output Frequency
RUN Command
Frequency
AUTO LED
HAND Mode Selection
AUTO Mode Selection
OFF
AUTO
Operation Mode
OFF
HAND LED
OFF
0 Hz
6 Hz
ON
Short blink
Figure 4.7 LEDs and Drive Operation in AUTO and HAND Modes
u
Setting the Real Time Clock
The time and date must be set when a new HOA keypad is plugged in and the drive is powered up. The HOA keypad will
display the time and date setup screen for 30 seconds. If a button is not pressed during this time, the display will clear and a
“Clock Not Set” alarm will flash. Pressing the F2 (Data) key will display the setting screen again.
n
Feedback Loss Wire Break Alarm
If there is no sensor wired to the drive, a “Feedback Loss – Wire Break” alarm will flash on the display. Providing the proper
feedback device signal will clear the Feedback Loss alarm.
The drive requires a feedback device (e.g., pressure transducer, flow meter, etc.) to perform automatic system regulation. Any
analog 0~10 V or 4-20 mA feedback device can be used in combination with the drive.
Note:
The factory default setting for the drive is 4~20 mA feedback device connected to analog input A2.
n
Real Time Clock Setting Display
Note:
Setting the Real-Time Clock will clear a “Clock Not Set” alarm.
4.6 Using the Optional HOA Keypad
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
77
4
Start-Up Programming & Operation