H2: Multi-Function Output
n
H2-01 to H2-03: Terminal MA/MB/MC, P1/PC, and P2/PC Function Selection
The drive has three multi-function output terminals.
No.
Parameter Name
Setting Range
Default
H2-01
Terminal MA, MB and MC Function Selection (relay)
0 to 1AA
E: Fault
H2-02
Terminal P1 Function Selection (open-collector)
0 to 1AA
37: During Frequency Output
H2-03
Terminal P2 Function Selection (open-collector)
0 to 1AA
E: Fault
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 5.51 During Run Time Chart
Setting 1: Zero Speed
Terminal closes when the output frequency falls below the minimum output frequency set to E1-09 or b2-01.
Status
Description
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
OFF
Output frequency
or
motor speed
Zero Speed
ON
E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)
Figure 5.52 Zero-Speed Time Chart
Setting 2: Speed Agree 1 (f
ref
/f
out
Agree 1)
Closes when the actual output frequency is within the Speed Agree Width (L4-02) of the current frequency reference regardless
of the direction.
Status
Description
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note:
Detection works in forward and reverse.
5.7 H: Terminal Functions