Bias
Output
frequency
Up 2 command
d4-06 value
5 s
Bias is saved in parameter d4-06
5 s
Figure 5.35 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note:
Make sure to set the Up/Down 2 limits properly when using d4-01 = 1 in combination with the Up/Down 2 function.
Frequency Reference Bias Upper Limit (Up/Down 2) on page 154
Refer to d4-09: Frequency Reference Bias Lower Limit (Up/
for details on the limit settings.
Clearing the Value that was Saved
Depending on which function is used, the frequency reference value that was saved can be cleared by:
• Releasing the acceleration hold input.
• Setting an Up or Down command while no Run command is active.
n
d4-03: Frequency Reference Bias Step (Up/Down 2)
Sets the bias that is added to or subtracted from the frequency reference by the Up/Down 2 function.
No.
Parameter Name
Setting Range
Default
d4-03
Frequency Reference Bias Step
0.00 to 99.99 Hz
0.00 Hz
The operation depends on the set value:
Setting d4-03 = 0.0 Hz
While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel time determined
by parameter d4-04.
Bias
Output
frequency
Bias value is increased using the
accel/decel times as set in d4-04
Up 2 command
Figure 5.36 Up/Down 2 Bias when d4-03 = 0.0 Hz
5.4 d: Reference Settings
152
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual