Drive
Model
Terminal
Recomm.
Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening
Torque
N•m (lb.in.)
4V0031
R/L1, S/L2, T/L3
8
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
10 to 6
, 1, 2
–
10 to 6
B1, B2
–
14 to 10
2.7 to 3.0
(23.9 to 26.6)
6
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
4V0038
R/L1, S/L2, T/L3
6
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
10 to 6
, 1, 2
–
10 to 6
B1, B2
–
10 to 8
2.7 to 3.0
(23.9 to 26.6)
6
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
u
Main Circuit Terminal Power Supply and Motor Wiring
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
NOTICE:
When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE:
Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to
comply may result in abnormal operation of drive and nearby equipment.
NOTICE:
Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper application of noise filters could
result in damage to the drive.
NOTICE:
Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious
injury by fire as a result of drive damage from line voltage application to output terminals.
n
Cable Length Between Drive and Motor
When the cable length between the drive and the motor is too long (especially at low frequency output), note that the cable
voltage drop may cause reduced motor torque. Drive output current will increase as the leakage current from the cable increases.
An increase in leakage current may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the drive carrier frequency according to the following table. If the motor wiring distance exceeds 100 m because of the
system configuration, reduce the ground currents.
Refer to
to set the carrier frequency to an appropriate level.
Table 3.7 Cable Length Between Drive and Motor
Cable Length
50 m or shorter
100 m or shorter
Longer than 100 m
Carrier Frequency
15 kHz or less
5 kHz or less
2 kHz or less
Note:
When setting carrier frequency, calculate the cable length as the total distance of wiring to all connected motors when running multiple
motors from a single drive.
n
Ground Wiring
Follow the precautions to wire the ground for one drive or a series of drives.
WARNING!
Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize
the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could
result in death or serious injury.
WARNING!
Electrical Shock Hazard. Be sure to ground the drive ground terminal. (200 V Class: Ground to 100 Ω or less, 400 V Class:
Ground to 10 Ω or less). Improper equipment grounding could result in death or serious injury by contacting ungrounded electrical equipment.
NOTICE:
Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper
equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE:
When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in
abnormal operation of drive or equipment.
when using multiple drives. Do not loop the ground wire.
3.6 Main Circuit Wiring
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
53
3
Electrical Installation