User Constant Tables
5-
29
Multi-function Contact Output Functions
Note Set to 0F when contact input is used for the built-in PLC or not used as multi-function contact input.
Setting
Value
Function
Control Methods
Open
Loop
Vector
Flux
Vector
00
During run (on: Run command is on or voltage is being output)
Yes
Yes
01
Zero-speed
Yes
Yes
02
Frequency (speed) agree 1 [L4-02 (detection width) is used]
Yes
Yes
03
Desired frequency (speed) agree 1 [on: Output frequency =
±
L4-01, L4-02 (detection width) is
used and during frequency agree]
Yes
Yes
04
Frequency (FOUT) detection 1 [on: +L4-01
≥
Output frequency
≥
-L4-01, L4-02 (detection
width) is used]
Yes
Yes
05
Frequency (FOUT) detection 2 [on: Output frequency (speed)
≥
+L4-01 or output frequency
≤
-
L4-01, L4-02 (detection width) is used]
Yes
Yes
06
Inverter operation ready (operation ready: Normal status without error after initialization)
Yes
Yes
07
During main circuit undervoltage (UV) detection
Yes
Yes
08
During baseblock (on: during baseblock)
Yes
Yes
09
Frequency reference selection (on: Frequency reference from operator)
Yes
Yes
0A
Run command selection status (on: Run command from operator)
Yes
Yes
0B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detection when
on)
Yes
Yes
0C
Loss of frequency reference [Effective when L4-05 (operation selection when frequency refer-
ence is lost) is set to 1]
Yes
Yes
0E
Fault (on: Error other than CPF00 and CPF01 has occurred)
Yes
Yes
0F
Not used (Set when the terminal is used for the built-in PLC or not used.)
Yes
Yes
10
Minor fault (on: Alarm displayed)
Yes
Yes
11
Fault reset command active
Yes
Yes
13
Frequency (speed) agree 2 [L4-04 (detection width) is used]
Yes
Yes
14
Desired frequency (speed) agree 2 [on: Output frequency = L4-03, L4-04 (detection width) is
used, and frequency agree]
Yes
Yes
15
Frequency (FOUT) detection 3 [on: Output frequency
≤
L4-03, L4-04 (detection width) is used]
Yes
Yes
16
Frequency (FOUT) detection 4 [on: Output frequency
≥
L4-03, L4-04 (detection width) is used]
Yes
Yes
17
Overtorque/undertorque detection 1 NC (NC contact: Overtorque/undertorque detection when
off)
Yes
Yes
18
Overtorque/undertorque detection 2 NO (NO contact: Overtorque/undertorque detection when
on)
Yes
Yes
19
Overtorque/undertorque detection 2 NC (NC contact: Overtorque/undertorque detection when
off)
Yes
Yes
1A
During reverse run (on: During reverse run)
Yes
Yes
1B
During baseblock 2 (off: During baseblock)
Yes
Yes
1D
During regeneration (on: During regeneration)
No
Yes
1E
Restart enabled (on: Restart enabled)
Yes
Yes
1F
Motor overload (OL1)
Yes
Yes
30
During torque limit (current control) (on: During torque limit)
Yes
Yes
31
During speed limit (on: During speed limit)
No
Yes
37
During run 2 (on: Frequency output, off: Base block, DC injection braking, initial excitation,
operation stop)
Yes
Yes