![YASKAWA FSDrive-MV1S Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/yaskawa/fsdrive-mv1s/fsdrive-mv1s_instructions-manual_3478741026.webp)
1
-12
Transportation and Installation
Transporting the FSDrive-MV1S Series Inverter
•
To lift the small/middle capacity (3 kV class 200 to 2300 kVA, 6 kV class 400 to 2300 kVA) Inverter, use
the fixtures indicated on the panels.
•
To lift the large capacity (3 kV class 3000 kVA, 6 kV class 3000 to 6000 kVA) Inverter, use the lifting tool
provided as an accessory to lift only the Transformer Panel.
•
Never climb on the panel top.
The exhaust louver on the panel top can be easily damaged by external force.
Side-by-Side Installation
For Inverters of capacity 2300 kVA or more of both 3 kV class and 6 kV class, the panels are designed to be
installed side-by-side.
For these models, eight (8) holes are provided each on the Transformer Panel frame and Power Cell Panel
frame as shown in
Use M10×30L bolts, washers, and S washers to joint the panels.
Fig 1.4 Mounting Holes for Side-by-Side Installation (Example of 3 kV 2300 kVA Inverter)
Movement of the Inverter with a crane must be performed only by a qualified crane oper-
ator.
Failure to observe this precaution may result in injury or in dropping the Inverter.
CAUTION
Transformer Panel
Cell Panel