b3-14
Current control start
level during voltage
restoration
Sets the level to start prolonga-
tion of voltage restoration time
to control current during speed
search. Set the level as no-load
current = 1.0.
0.0 to
5.0
2.0
No
A
A
1CDH
Srch Lvl Red I
b3-15
Time constant for
current control during
voltage restoration
Sets the time constant for filter-
ing for the level to prolong
voltage restoration time in
order to control current during
speed search.
0 to
100
5 ms
No
A
A
1CEH
Srch T Red I
b3-16
Wait time after
completion of speed
search
Sets the wait time for switching
to normal control after comple-
tion of speed search. The fre-
quency reference will be held
during the set wait time.
0.00 to
5.00
0.01 s
No
A
No
1CFH
SpdSrch Ret Time
b3-17
Software CLA current
limit 1 during speed
search
Sets the software current limit
value at speed search in per-
centage to the motor rated cur-
rent.
0.0 to
300.0
100.0%
No
A
A
1D0H
SpdSrch CLA Lvl1
b3-18
Software CLA current
limit 2 during speed
search
Sets the software current limit
value at 0 Hz at speed search in
percentage to the motor rated
current.
0.0 to
300.0
100.0%
No
A
A
1D1H
SpdSrch CLA Lvl2
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display