Stopping Methods
6-
7
Setting Precautions
•
When using flux vector control, the zero-speed control starts when motor speed drops to b2-01 during
deceleration. Also, the setting b2-01
<
E1-09 is possible.
•
The current level during injection brake time at start is the value of E2-03 (motor no-load current). Accord-
ingly, b2-02 is invalid in flux vector control.
Coast to Stop
If the Stop Command is input (i.e., the Run Command is turned off) when b1-03 is set to 1, the Inverter output
voltage is interrupted. The motor coasts to a stop at the deceleration rate that counterbalances damage to the
machine and inertia including the load.
Fig 6.5 Coast to Stop
INFO
After the Stop Command is input, Run Commands are ignored until the Minimum Baseblock Time (L2-03) has
elapsed.
Output frequency
Run command
On
Off
Inverter output freqeuencty interrupted.