![YASKAWA FSDrive-MV1S Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/yaskawa/fsdrive-mv1s/fsdrive-mv1s_instructions-manual_3478741036.webp)
Wiring Main Circuit Terminals
2-
7
Wiring the Main Circuits
This section describes wiring for the main circuit inputs and outputs, and grounding.
Make sure, for each terminal code, to correctly connect the input terminals to the power supply and the output
terminals to the load.
Wiring the Main Circuit Input Terminals
Observe the following when wiring the main circuit input terminals.
Terminal Block Construction and Cable End Processing
Prepare appropriate cable brackets for the cable size.
Connection to the Terminal Block
The input power supply can be connected to any of terminals R, S, or T on the terminal block, as the phase
sequence of input power supply is irrelevant to the phase sequence. However, we recommend that you connect
in the same sequence as the input power supply for product maintainability.
IMPORTANT
A line-to-line voltage drop must be taken into consideration when selecting wire size.
Determine the wire size for the main circuit so that the line-to-line voltage drop is within 2% of the rated volt-
age. The line-to-line voltage drop is calculated as follows.
Line-to-line voltage drop (V) =
x Wire resistance (
Ω
/km) x Wire length (m) x Current (A) x 10
-3
Incorrect wiring of I/O terminals will damage the Inverter when the power supply is
turned on, and may result in injury.
3
CAUTION