Monitor Constants
6-
51
Monitor Constants
This section explains the analog monitor and pulse monitor constants.
Using the Analog Monitor Constants
This section explains the analog monitor constants.
Related Constants
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
H4-01
Monitor selection
(terminal AO1)
Sets the number of the monitor
item to be output (U1-
)
from terminal AO1.
0 to 99
2
Yes
A
A
470H
Term AO1 Signal
H4-02
Gain (terminal AO1)
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0 to
30.00
1.00
Yes
A
A
471H
Term AO1 Gain
H4-03
Bias (terminal AO1)
Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-100.0
to
100.0
0.0%
Yes
A
A
472H
Term AO1 Bias
H4-04
Monitor selection
(terminal AO2)
Sets the number of the monitor
item to be output (U1-
)
from terminal AO2.
0 to 99
3
Yes
A
A
473H
Term AO2 Signal
H4-05
Gain (terminal AO2)
Sets the multi-function analog
output 2 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
0 to
30.00
1.00
Yes
A
A
474H
Term AO2 Gain
H4-06
Bias (terminal AO2)
Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
-100.0
to
100.0
0.0%
Yes
A
A
475H
Term AO2 Bias
H4-07
Monitor selection
(terminal AO3)
Sets the number of the monitor
item to be output (U1-
)
from terminal AO3.
0 or 99
5
Yes
A
A
476H
Term AO3 Signal