Operation Errors
An operation error will occur if there is an invalid setting or a contradiction between two constant settings. It
won't be possible to start the Inverter until the constants have been set correctly. (The alarm output and fault
contact outputs will not operate either.)
When an operation error has occurred, refer to the following table to identify and correct the cause of the
errors.
Table 7.3 Operation Error Displays and Incorrect Settings
Display
Meaning
Incorrect settings
OPE02
Limit
Constant Setting Range
Error
The constant setting is outside of the valid setting range. Press the ENTER Key on
the Digital Operator to display OPE fault constant (U1-34).
OPE03
Terminal
Multi-function Input
Selection Error
One of the following errors has been made in the multi-function input (H1-01 to H1-
10) settings:
• The same setting has been selected for two or more multi-function inputs.
• An up or down command was selected independently. (They must be used
together.)
• The up/down commands (10 and 11) and Accel/Decel Ramp Hold (A) were
selected at the same time.
• Speed Search 1 (61, maximum output frequency) and Speed Search 2 (62. set fre-
quency) were selected at the same time.
• The up/down commands (10 and 11) were selected while PID Control Method
Selection (b5-01) was enabled.
• Positive and negative speed commands have not been set at the same time.
• The emergency Stop Command NO and NC have been set at the same time.
OPE07
Analog
Selection
Multi-function Analog
Input Selection Error
The same setting has been selected for two or more multi-function analog inputs.
OPE08
Ctrl Func
Error
Constant Selection
Error
A setting has been made that is not required in the current control method. Ex.: A
function used only with open-loop vector control was selected for flux vector con-
trol. Press the ENTER Key on the Digital Operator to display OPE fault constant
(U1-34).
OPE10
V/f Ptrn Set-
ting
V/f Data Setting Error
Constants E1-04, E1-06, E1-07, and E1-09 do not satisfy the following conditions:
• E1-04 (FMAX)
≥
E1-06 (FA) > E1-07 (FB)
≥
E1-09 (FMIN)
OPE11
Carr Freq/
On-Delay
Constant Setting Error
The motor overload detection start level (L1-06) has been set to a value above the
motor overload detection level (L1-07).
ERR
EEPROM
R/W Err
EEPROM Write Error
A verification error occurred when writing EEPROM.
• Try turning the power supply off and on again.
• Try setting the constants again.