Checking and Controlling the Installation Site
Install the Inverter in the installation site as described below and maintain optimum conditions.
Installation Site
Install the Inverter at a location that satisfies the following requirements.
•
Ambient temperature:
-
5 to +40
°
C
•
Relative humidity: 85%RH max. without condensation
•
Free from dripping water
•
Free from corrosive liquid or gas
•
Not subjected to excessive dust and iron powder
•
Not subjected to excessive vibration
Refer to the dimensional drawings of each Inverter model for the space required for installation. If the Inverter
must be installed in a location subjected to excessive vibration caused by machines such as cranes, contact
your Yaskawa representative. The Inverter generates noise, including radio noise, to some extent; this should
be considered when selecting the installation location.
Required Space Around Panels
Keep space as described below around the panels to maintain sufficient cooling of the Inverter.
If the installation space is so limited that the described space cannot be reserved around the panels, contact
your Yaskawa representative.
1. Space Above the Panels
Keep a distance of one meter or more between the panel top and the room ceiling.
A cooling fan is provided on the top of each panel so that air flows upward. If the room ceiling is too
low, pressure loss increases and the required cooling air flow cannot be maintained.
Additionally, sufficient space for removing the cooling fan from the panel top is required for replace-
ment.
2. Space in Front of the Panels
Keep a space of two meters or more in front of each panel to allow for maintenance.
Space for a lifter to draw out the primary switchgear and the cell unit in the Power Cell Panel is
required.
3. Space Behind the Panels
Keep a space of 60 cm or more behind each panel to allow for maintenance.
This space is required when leading the cable into the primary switchgear and installing anchors on
the back of Power Cell Panel.