User Constant Tables
5-
9
* The factory setting will change when the control method is changed.
DC Injection Braking: b2
User constants for injection braking are shown in the following table.
b1-07
Operation selection
after switching to
remote mode
Used to set the operation mode
by switching to the Remote
mode using the Local/Remote
Key.
0: Run signals that are input
during mode switching are
disregarded. (Input Run
signals after switching the
mode.)
1: Run signals become
effective immediately after
switching to the Remote
mode.
0 or 1
0
No
A
A
1A6H
LOC/REM RUN Sel
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
b2-01
Zero-speed level (DC
injection braking
starting frequency)
Used to set the frequency
which starts DC injection brak-
ing in 1% units when decelera-
tion to stop is selected.
When b2-01 is less than E1-09,
E1-09 becomes the DC injec-
tion braking starting frequency.
* The factory setting will change
when the control method is
changed.
0.00 to
10.00
0.50%
*
No
A
A
1B0H
DCInj Start Freq
b2-02
DC injection braking
current
Sets the DC injection braking
current as a percentage of the
Inverter rated current.
0 to
100
50%
No
A
No
1B1H
DCInj Current
b2-03
DC injection braking
time at start
Used to set the time to perform
DC injection braking at start in
units of 1 second.
Used to stop coasting motor
and restart it. When the set
value is 0, DC injection braking
at start is not performed.
0.00
to
10.00
0.00
s
No
A
A
1B2H
DCInj Time@Start
b2-04
DC injection braking
time at stop
Used to set the time to perform
DC injection braking at stop in
units of 1 second.
Used to prevent coasting after
the Stop Command is input.
When the set value is 0.00, DC
injection braking at stop is not
performed.
0.00
to
10.00
0.50
s
No
A
A
1B3H
DCInj Time@Stop
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display