5
-4
A: Setup Settings
The following settings are made with the environment constants (A constants): Language displayed on the
Digital Operator, access level, control method, initialization of constants.
Initialize Mode: A1
User constants for the environment modes are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
A1-00
Language selection for
Digital Operator
display
Used to select the language dis-
played on the Digital Operator
(LCD).
0: English
1: Japanese
2: Chinese
0 to 2
1
Yes
A
A
100H
Select Language
A1-01
Constant access level
Used to set the constant access
level (set/read.)
0: Monitoring only
(Monitoring drive mode and
setting A1-01 and A1-04.)
2: Advanced
(Constants can be read and
set in both quick
programming mode and
advanced programming (A)
mode.)
0 to
9999
2
No
A
A
101H
Access Level
A1-02
Control method
selection
2: Open-loop vector control
3: Flux vector control
This constant is not initialized
by the initialize operation.
2, 3
2
No
Q
Q
102H
Control Method
A1-03
Initialize
Used to initialize the constants
using the specified method.
0:
No initializing
2220: Initializes using a two-
wire sequence.
(Initializes to the
factory setting.)
0 to
9999
0000
No
A
A
103H
Init Parameters
A1-04
Password
(Manufacturer’s password
number)
0 to
9999
0
No
A
A
104H
Enter Password
A1-11
Year setting
Used to set the years of cal-
ender.
0 to
99
−
No
A
A
10BH
Year
A1-12
Month and Date
setting
Used to set the months and the
days of calender.
1.01 to
12.31
−
No
A
A
10CH
Month/Date
A1-13
Hour and Minute
setting
Used to set the minutes and the
seconds of calender.
0.00 to
23.59
−
No
A
A
10DH
Hour/Minute