![YASKAWA FSDrive-MV1S Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/yaskawa/fsdrive-mv1s/fsdrive-mv1s_instructions-manual_3478741035.webp)
2
-6
Applicable Wire Sizes and Crimp Terminals
Refer to
to select appropriate wires and crimp terminals for main circuit wiring and grounding.
Table 2.3 Terminal Screw Size and Applicable Wire Sizes
Volt-
age
Class
Fre-
quency
[Hz]
Model
CIMR-MV1
Rated
Current
[A]
Terminal
Terminal
Screw
Size
Tightening
Toque
[N·cm]
Applicable Wire Size
[mm
2
] (AWG)
Func-
tion
Code
3 kV
50/60
132
35
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
60
Ground
EA
M5
2.0 to 2.5
5.5 to 14 (10 to 6)
200
50
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
60
Ground
EA
M5
2.0 to 2.5
5.5 to 14 (10 to 6)
315
70
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
80
Ground
EA
M6
4.0 to 4.9
5.5 to 22 (10 to 4)
450
100
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
38 to 100 (2 to 4/0)
125
Ground
EA
M8
8.9 to 10.8
5.5 to 38 (10 to 2)
630
140
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
38 to 100 (2 to 4/0)
150
Ground
EA
M8
8.9 to 10.8
22 to 60 (4 to 0)
900
200
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
38 to 100 (2 to 4/0)
200
Ground
EA
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
13C
260
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
60 to 100 (0 to 4/0)
300
Ground
EA
M10
18.0 to 23.0
22 to 150
(4 to 300MCM)
18C
400
I/O
R, S, T, U, V, W
M12
31.5 to 39.5
150 to 325
(300MCM to 600MCM)
400
Ground
EA
M12
31.5 to 39.5
60 to 200
(0 to 400MCM)
25C
520
I/O
R, S, T, U, V, W
M12
31.5 to 39.5
150 to 325
(300MCM to 600MCM)
600
Ground
EA
M16
78.5 to 98.0
150 to 325
(300MCM to 600MCM)
6 kV
50/60
250
35
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
60
Ground
EA
M5
2.0 to 2.5
5.5 to 14 (10 to 6)
400
50
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
60
Ground
EA
M5
2.0 to 2.5
5.5 to 14 (10 to 6)
630
70
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
80
Ground
EA
M6
4.0 to 4.9
5.5 to 22 (10 to 4)
900
100
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
38 to 100 (2 to 4/0)
125
Ground
EA
M8
8.9 to 10.8
5.5 to 38 (10 to 2)
13C
140
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
38 to 100 (2 to 4/0)
150
Ground
EA
M8
8.9 to 10.8
22 to 60 (4 to 0)
18C
200
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
38 to 100 (2 to 4/0)
200
Ground
EA
M10
18.0 to 23.0
22 to 100 (4 to 4/0)
25C
260
I/O
R, S, T, U, V, W
M10
18.0 to 23.0
60 to 100 (0 to 4/0)
300
Ground
EA
M10
18.0 to 23.0
22 to 150
(4 to 300MCM)
36C
400
I/O
R, S, T, U, V, W
M12
31.5 to 39.5
150 to 325
(300MCM to 600MCM)
400
Ground
EA
M12
31.5 to 39.5
60 to 200
(0 to 400MCM)
50C
520
I/O
R, S, T, U, V, W
M12
31.5 to 39.5
150 to 325
(300MCM to 600MCM)
600
Ground
EA
M16
78.5 to 98.0
150 to 325
(300MCM to 600MCM)