8. Specifications
The chapter lists the specifications of UPS.
8.1
Conformity And Standards
The UPS has been designed to conform to the European and international standards listed in
Table
8-1
.
Table 8-1
: European and international standards
* Safety
Safety Conformance: IEC/EN 62040-1,UL1778 (5th Edition)
Safety Markings : cTUVus, CE
* EMI
Conducted Emission..............................: FCC PART15 CLASS A
Radiated Emission.................................: FCC PART15 CLASS A
*EMS
ESD.........................................................:IEC/EN 61000-4-2
Level 4
RS........................................................ ...:IEC/EN 61000-4-3
Level 3
EFT......................................................... :IEC/EN 61000-4-4
Level 4
SURGE................................................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
8.2 Environmental Characteristics
Table 8-2:
Environmental characteristics
Item
Unit
Specifications
Noise within 1 m
dB
Max. 75
Altitude
m
≤1000, derate powe
r by 1% per 100m
Relative humidity
% RH
0 ~ 95, non-condensing
Operating temperature
°C
0 ~ 40°C
Storage and transport
temperature for UPS
°C
-15 ~ 60°C
8.3 Mechanical Characteristics
Table 8-3
: Mechanical characteristics
42U cabinet
Model
Unit
X90-ENC2S
Rated power
kVA/kW
140
Dimensions, W x D x H
mm
600 x 1100 x 2010
Weight
kg
392
Color
N/A
Black
3U Power Module
Model
Unit
X90-PM50
X90-PM70
Rated power
kVA/kW
50KVA/50KW
70KVA/70KW
Содержание X90-2S
Страница 10: ...2 5 UPS Cabinet Model X90 2S Drawing Cabinet Height 42U Monitor Module 1 Max Power Module 2 Max Power 140kVA...
Страница 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Страница 15: ...Figure 2 13 Terminal Blocks...
Страница 17: ...Off There is neither a fault nor an alarm...
Страница 22: ......
Страница 29: ...3 Operation Mode and UPS Operation 3 1 Block diagram of UPS Wiring diagram for dual inputs Figure 3 1...
Страница 37: ......
Страница 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Страница 42: ......
Страница 53: ...Figure 4 6 Control screen page...
Страница 55: ...Figure 4 9 System Measurement Screens...
Страница 56: ...Figure 4 10 Module Measurement Screens...
Страница 88: ......