Figure 4-30 Reset All Events Confirmation screen
4.3 Alarm List
In
Table 4-12
is the complete list of UPS alarm messages.
Table 4-12
: Alarm List
Text recorded in event lists shown
on the LCD
Explanation
Fault! <01>Bus start fail
BUS soft start failed
Fault! <02>Bus over
BUS voltage high
Fault! <03>Bus under
BUS voltage low
Fault! <04>Bus unbalance
BUS voltage unbalanced
Fault! <06>Conv over cur
Converter over current
Fault! <11>INV start fail
Inverter soft start failed
Fault! <12>High INV VOL
Inverter voltage high
Fault! <13>Low INV VOL
Inverter voltage low
Fault! <14>INV A out SC
Phase A (Line to Neutral) output short circuited
Fault! <15>INV B out SC
Phase B (Line to Neutral) output short circuited
Fault! <16>INV C out SC
Phase C (Line to Neutral) output short circuited
Fault! <17>INV AB out SC
Phase A-Phase B (Line to Line) output short circuited
Fault! <18>INV BC out SC
Phase B-Phase C (Line to Line) output short circuited
Fault! <19>INV AC out SC
Phase C-Phase A (Line to Line) output short circuited
Fault! <1A>INV A N-fault
Phase A output negative power fault
Fault! <1B>INV B N-fault
Phase B output negative power fault
Fault! <1C>INV C N-fault
Phase C output negative power fault
Fault! <21>BATT SCR SC
Battery SCR short circuited
Fault! <23>INV relay open
Inverter relay open
Fault! <25>In&out swop
Line wiring fault
Fault! <29>BATT fuse broken
Battery fuse open
Fault! <31>Par commu fail
Parallel communication failed
Fault! <36>Par out cur unb
Parallel output current unbalanced
Содержание X90-2S
Страница 10: ...2 5 UPS Cabinet Model X90 2S Drawing Cabinet Height 42U Monitor Module 1 Max Power Module 2 Max Power 140kVA...
Страница 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Страница 15: ...Figure 2 13 Terminal Blocks...
Страница 17: ...Off There is neither a fault nor an alarm...
Страница 22: ......
Страница 29: ...3 Operation Mode and UPS Operation 3 1 Block diagram of UPS Wiring diagram for dual inputs Figure 3 1...
Страница 37: ......
Страница 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Страница 42: ......
Страница 53: ...Figure 4 6 Control screen page...
Страница 55: ...Figure 4 9 System Measurement Screens...
Страница 56: ...Figure 4 10 Module Measurement Screens...
Страница 88: ......