5. Interface and Communication
5.1 Dry Contact Port
As shown in figure 5-1, the Monitor Module includes dry contact ports (
③
~
④
), Extra Comm. slot,
SNMP slot, LCD connection port, STS Power LED and serial communication ports (RS232 port, USB
port, RJ45 to RS232 port) on the front panel.
Figure 5-1 Front view of Monitor module
5.1.1 X1-Remote EPO Input Port
The Emergency Power off (EPO) function in UPS can be operated by an assigned remote contact.
Logic N.C. turns off the UPS.
X1 is the remote EPO input port. The port is shown in Figure 5-2 and described in
Table 5-1
.
Figure 5-2 Remote EPO input port
Table 5-1:
Description of remote EPO port
EPO Logic Setting
Position
Description
Short
X1.1 & X1.2
EPO is not activated when X1.1 & X1.2 shortened
Open
X1.1 & X1.2
EPO is activated when X1.1 & X1.2 opened
EPO Logic setting is Normal Closed (N.C), EPO is triggered when pins 1 and 2 of X1 are opened.
Note:
1.
EPO function activates shutdown of the rectifiers, inverters and static transfer switch. But it
does not internally disconnect the input power supply.
5.1.2 X4-Maintenance Bypass Switch State Port
X4 is the maintenance bypass switch port. The port is shown in Figure 5-3 and described in
Table
Содержание X90-2S
Страница 10: ...2 5 UPS Cabinet Model X90 2S Drawing Cabinet Height 42U Monitor Module 1 Max Power Module 2 Max Power 140kVA...
Страница 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Страница 15: ...Figure 2 13 Terminal Blocks...
Страница 17: ...Off There is neither a fault nor an alarm...
Страница 22: ......
Страница 29: ...3 Operation Mode and UPS Operation 3 1 Block diagram of UPS Wiring diagram for dual inputs Figure 3 1...
Страница 37: ......
Страница 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Страница 42: ......
Страница 53: ...Figure 4 6 Control screen page...
Страница 55: ...Figure 4 9 System Measurement Screens...
Страница 56: ...Figure 4 10 Module Measurement Screens...
Страница 88: ......