Step 3
Please enter LCD SETUP MENU and choose
“
SYSTEM
”
to ensure
that the
“B
ypass mode
”
is enabled.
If the “Bypass mode” is
disabled, you have to change it to
“enabled”. Then, exit the SETUP
menu and check if the UPS operates in bypass mode.
Step 4
Turn off Maintenance Bypass Breaker as shown below.
ON
OFF
I
0
Step 5
Lock back the mechanical lock plate as shown below.
Содержание X90-2S