Dimensions, W x D x H
mm
750 x 438 x 130
750 x 438 x 130
Weight
kg
47
48
8.4 Electrical Characteristics (Input Rectifier)
Table 8-4:
Rectifier AC input (mains)
Rated power (kVA)
Unit
50~140
Rated AC input voltage
Vac
480(Ph-Ph)
Input voltage tolerance
Vac
383~520; 330~382(output derated below
50%)
Frequency
Hz
50/60 (tolerance: 40Hz ~ 70Hz)
Power factor
kW/kVA
0.99 at full load) or 0.98 at half load
Harmonic current distortion
THDI%
<4 (full load)
Nominal current / phase
A
50kVA/50kW
62
100kVA/100kW
87
70kVA/70kW
124
140kVA/140kW
174
Icc
kA
≤
10kA
8.5 Electrical Characteristics (Intermediate DC Circuit)
Table 8-5
: Battery
Intermediate DC circuit
Battery
External battery
Number of lead-acid
cells
Nominal
216 (6cells x 36 12V battery blocks)
Maximum
240 (6cells x 40 12V battery blocks)
Minimum
192 (6cells x 32 12V battery blocks)
Float voltage
V/cell
2.28V/cell
Temperature
compensation
mV/
℃
/cl 0~-5 (optional)
Ripple voltage
% V float
≤1
Ripple current
% C10
≤5
Boost voltage
VRLA
2.35V/cell
EOD voltage
V/cell
1.67-1.83V/cell (adjustable)
Battery charge
V/cell
Constant current and constant voltage charge mode
Battery charging
power
1
max
current
A
18A / per power module (adjustable)
Note
:
1. At low input voltage the UPS recharging capability increases (up to the maximum capacity
indicated).
8.6 Electrical Characteristics (Inverter Output)
Table 8-6:
Inverter output (to load)
Rated power (kVA)
Unit 140
Rated AC voltage
1
Vac
480 (three-phase three-wire)
Frequency
Hz
50/60 Auto Select
Содержание X90-2S
Страница 10: ...2 5 UPS Cabinet Model X90 2S Drawing Cabinet Height 42U Monitor Module 1 Max Power Module 2 Max Power 140kVA...
Страница 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Страница 15: ...Figure 2 13 Terminal Blocks...
Страница 17: ...Off There is neither a fault nor an alarm...
Страница 22: ......
Страница 29: ...3 Operation Mode and UPS Operation 3 1 Block diagram of UPS Wiring diagram for dual inputs Figure 3 1...
Страница 37: ......
Страница 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Страница 42: ......
Страница 53: ...Figure 4 6 Control screen page...
Страница 55: ...Figure 4 9 System Measurement Screens...
Страница 56: ...Figure 4 10 Module Measurement Screens...
Страница 88: ......