3.3 UPS Operation
⚫
Do not start the UPS until the installation is completed.
⚫
Make sure the wiring is correct and the power cables are fixed firmly.
⚫
Make su
re the Power Modules’ address
IDs have been configured. Refer to section 2.9.2
⚫
Make sure the ready switch on the Power Module has been switched
to the “Locked”
position.
⚫
Make sure all the breakers are switched
OFF
.
3.3.1 AC Startup
Ensure to follow this procedure when turning on the UPS from a fully powered-down state.
The operating procedures are:
Step 1
: Refer to
“
Chapter 2 Installation
”
to connect the power cables and install the Power
Modules and the battery required for the UPS system.
Step 2
: Switch ON the battery breaker.
Step 3
: Switch ON the external power switch in a distribution panel to power the UPS.