Figure 4-18 Setup-Pre-Alarm screen
Table 4-10
: Setup-Pre-Alarm setting list
Setting Item Sub Item
Explanation
Line Voltage
Range
--
Set line voltage range:
Upper limit
⚫
+5%
⚫
+10%
⚫
+15%
⚫
+20% (Default)
Lower limit
⚫
-5%
⚫
-10%
⚫
-15%
⚫
-20% (Default)
Line
Frequency
Range
--
Set line frequency range:
Upper / Lower limit
⚫
+/- 1Hz
⚫
+/- 2Hz
⚫
+/- 3Hz
⚫
+/- 4Hz (Default)
Load
--
Set UPS Overload percentage (40~100%)
⚫
100% (Default)
Set UPS load unbalance percentage (20~100%)
⚫
100% (Default)
4.2.6.5 Setup-OTHERS Screen
Use UP and DOWN icons to switch between different sub-menus. Press ENTER icon to go into the
OTHERS
setting screen, as shown in Figure 4-19.