44
XL1
C0~C575
HC0~HC95
HSC0~HSC31
XL3
C0~C575
HC0~HC95
HSC0~HSC31
XL5
C0~C4999
HC0~HC1999
HSC0~HSC39
XL5E
C0~C4999
HC0~HC1999
HSC0~HSC39
XLME
C0~C4999
HC0~HC1999
HSC0~HSC39
The counter range:
Counter type
Explanation
16/32 bits up/down
counter
C0~C575 HC0~HC95 (32-bits counter occupies two registers, the
counter address must be even number)
High speed
counter
HSC0~HSC30 (HSC0,HSC2...HSC30) (each counter occupies two
registers, the counter address must be even number)
1: Please refer to chapter 5 for details of high speed counter.
2: XD/XL series counters can be 16 or 32 bits count up/down mode. The mode is appointed
by the instruction. Which means the same counter can be used as 16-bit or 32-bit. The
increment/subtraction counting mode is also specified by the instruction mode.
Item
16-bit counter
32-bit counter
Count direction
Count down/up
Count up/down
Set value
0~32,767
-2,147,483,648~+2,147,483,647
Set value type
Constant K or register
Constant K or a couple of registers
Count value
The value will not
change when reaching
the max or min value
The value will not change when reaching
the max or min value
Output
Keep the state for count
up
Reset for count down
Reset
Run RST instruction, the counter and output will be reset
Present count
value register
16-bit
32-bit
The soft component will appoint the type of counter: common counter or power-off retentive
counter.
The set value range of 16-bit count-up counter is K1~K32,767 (decimal). K0 and K1 have
the same function. They mean the counter output will act at the first counting.
If the PLC power supply is cut off, common counter value will be reset. The power-off
retentive counter value will be kept.
Counter
features
Function
16-bit common counter and power-off retentive counter
Содержание XD Series
Страница 1: ...XD XL series PLC User manual Instruction WUXI XINJE ELECTRIC CO LTD Data No PD05 20201022 3 5 ...
Страница 210: ...209 ...
Страница 314: ...313 B Double click the middle part to modify ...