376
ID
Function
Note
Serial
port 0
SD140
Modbus read write
instruction execution result
0: correct
100: receive error
101: receive overtime
180: CRC error
181: LRC error
182: station error
183: send buffer overflow
400: function code error
401: address error
402: length error
403: data error
404: slave station busy
405: memory error
(
erase
FLASH
)
SD141
X-Net communication
result
0: correct
1: communication overtime
2: memory error
3: receive CRC error
SD142
Free format
communication send result
0: correct
410: free format send buffer
overflow
SD143
Free format
communication receive
result
0: correct
410: send data length overflow
411: receive data short
412: receive data long
413: receive error
414: receive overtime
415: no start character
416: no end character
SD144
Free format
communication receive
data numbers
In bytes, there are no start and stop
characters
……
SD149
Serial
port 1
SD150
Modbus read write
instruction execution result
0: correct
100: receive error
101: receive overtime
180: CRC error
181: LRC error
182: station error
183: send buffer overflow
400: function code error
401: address error
402: length error
403: data error
404: slave station busy
405: memory error
(
erase
FLASH
)
SD151
X-Net communication
result
0: correct
1: communication overtime
communication
(
SD140~SD199
)