![Xinje XD Series Скачать руководство пользователя страница 344](http://html.mh-extra.com/html/xinje/xd-series/xd-series_user-manual_887444344.webp)
343
X5
I0300
I0301
SM053
X6
I0400
I0401
SM054
X7
I0500
I0501
SM055
X10
I0600
I0601
SM056
X11
I0700
I0701
SM057
X12
I0800
I0801
SM058
X13
I0900
I0901
SM059
Note: when the interruption ban coil is ON, the external interruption will not execute.
Enable Interruption [EI], Disable Interruption [DI], Interruption Return [IRET]
Note: In interrupt subroutine, only simple instructions such as set, reset, transmission and
operation can be written, which can be executed in a scanning cycle. Other instructions such
as sending pulses, timing (except for precise timing), communication and other instructions
that need to be continuously executed are not supported.
If use EI instruction to allow
interruption, then when scanning the
program,
if
interruption
input
changes from OFF to ON, then
execute subroutine
①、②
. Return to
the original main program.
Interruption pointer (I****) should
be behind FEND instruction;
PLC is usually on the status that
allows interruption.
Interruption Instruction