279
bit11
~
bit12
:
not useful
bit13
~
bit14 auto tune PID
mode (valid in critical
oscillation mode)
00
:
PID control
01
:
PI control
10
:
P control
bit15
:
0
:
regular mode
;
1
:
advanced mode;
S3+3
Proportion Gain (Kp)
Range
:
1
~
32767[%]
S3+4
Integration time (TI)
0
~
32767[unit: 100ms]
0 is taken as no
integral.
S3+5
Differential time ( TD)
0
~
32767[unit: 10ms]
0 is taken as no
differential.
S3+6
PID operation zone
0
~
32767
PID adjustment band
width value
S3+7
Control death zone
0
~
32767
PID output value
will not change in
death zone
S3+8
Sampling temperature
filter coefficient
0
~
100[%]
Filter the input
sampling
temperature in
advanced mode, 0 is
no input filter
S3+9
Differential gain( KD)
0
~
100[%]
Only for advanced
mode (normal mode
default value is
50%), 0 is no
differential gain
S3+10 Upper limit value of
output
0
~
32767
S3+11 Lower limit value of
output
0
~
32767
S3+12 Change of Unit
Temperature Corresponds
to Change of AD Value
full scale AD value *
(
0.3~1%
)
default value is 10
16-bit no sign, only
for step PID
S3+13 PID auto tune overshoot
0
:
enable overshoot
1
:
not overshoot
(
try to
reduce the overshoot
)
only for step PID
S3+14 Current target value
adjusting percentage
every time in auto tune
end transition stage
Cannot adjust
16-bit no sign, only
for step PID
S3+15 Number of times
exceeding the target value
in auto tune end transition
stage when limiting the
overshoot
only for step PID,
default value is 15
S3+16 PID type and status
Bit0~bit1
:
00: manual mode
01: step mode
Internal use
parameters of the
system for