244
Execution
Condition
Normally ON/OFF, edge
triggering
Suitable
models
XD, XL
Hardware
Requirement
-
Software
Requirement
-
Operands
Operands Function
Type
S1
Specify remote communication station number
16 bits
,
BIN
S2
Specify remote register start address
16 bits
,
BIN
S3
Specify register number
16 bits
,
BIN
D1
Specify start address of local register
16 bits
,
BIN
D2
Specify serial port number
16 bits
,
BIN
Suitable soft components
Notes: D includes D, HD; TD includes TD, HTD; CD includes CD, HCD, HSCD, HSD;
DM includes DM, DHM; DS includes DS, DHS.
REGR
K1
K500
K3
D1
X0
K2
S1·
S2·
S3·
D1·
D2·
Read register, Modbus function code is 03H.
Serial port: K0~K5. K0: Port0 (RS232), K1: Port1(RS232), K2: Port2(RS485), K3:
Port3(left extension port), K4: Port4(above extension port 1), K5: Port5(above
extension port 2).
Operand S3: max register number is 125.
When X0 is ON, REGR instruction is executed, Modbus read write flag SM160(serial
port2) is set ON, SM160 is set OFF when the execution is completed. If a
communication error occurs and the number of resend is set, it will be automatically
resend. Users can check the relevant registers to determine the cause of the error. The
execution result of Modbus read and write instructions of serial port 2 is in SD160.
Input register read [INRR]
Summary
Read remote station no’s input register to local device.
Word
Function
Operands
System
Constant
Module
D*
FD
TD*
CD*
DX
DY
DM*
DS*
K /H
ID
QD
S1
●
●
●
●
●
S2
●
●
●
●
S3
●
●
●
●
●
D1
●
D2
K