Appendix special soft device list
(unit: 0.1
℃
)
has sign (negative or positive). Unit is 0.1
℃
, the default value is 0.
The set temperature
value(unit: 0.1
℃
)
Control system’s target temperature value. The range is 0
~
1000
℃
, the precision is 0.1
℃
.
Temperature control
cycle (unit: 0.1s)
Control cycle’s range is 0.5s
~
200s, the minimum precision is 0.1s. The write value is the
real temperature control cycle multiplies 10. i.e. 0.5s control cycle should write 5, 200s
control cycle should write 2000.
Real value
(unit: 0.1
℃
)
If users think the environment temperature is different with the display temperature, he can
write in the known temperature value. At the moment of value written in, calculate the
temperature difference δ and save.
Calculate the temperature difference value δ=adjust environment temperature value
-
sample temperature value. Unit: 0.1
℃
.
E.g.: under heat balance status, user test the environmental temperature as 60.0
℃
with
mercurial thermometer, the display temperature is 55.0
℃
(correspond sample temperature
is 550), temperature difference δ=0. at this time, users write this parameters with 600
,
temperature difference δ is re-calculated to be 50 (5
℃
), then the display temperature =
(sample temperature
+
temperature difference δ
)
/10 =60
℃
。
**Note: when users write the adjust temperature value, make sure that the temperature is
same with the environment temperature value. This value is very important, once it’s
wrong, temperature difference δ will be wrong, then effect the display temperature
Auto tune output value
The output when auto tune, use % as the unit, 100 represents 100% of full scale output. 80
represent 80% of full scale output.
Appendix 1-4
.
Special Flash Register List
1
、
I filter
ID
Function
Initial Value
Description
FD8000
input filter time of
X
port
10
Unit: ms
FD8002
0
FD8003
0
……
0
FD8009
0
2
、
I mapping
ID
Function
Initial value
Description
FD8010
X00
corresponds with
I**
0
X0 corresponds with number of
input image I**
FD8011
X01
corresponds with
I**
1
Initial values are all decimal
FD8012
X02
corresponds with
I**
2
……
……
FD8073
X77
corresponds with
I**
63
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...