8 expansion devices
8-3-4
.
XC-E4DA
0V
24V
VO2
C3
AO2
C2
VO0
VO1
C0
AO0
C1
AO1
VO3
AO3
CH
NAME SIGNAL
CH
NAME SIGNAL
CH0
AO0
Current analogue output CH1 AO1
Current analogue output
VO0
Voltage analogue output
VO1
Voltage analogue output
C0
COM of CH0
C1
COM of CH1
Items
Voltage Output
Current Output
Analogue Output
Range
DC0
~
5V, 0
~
10V
(external
load
resistor
2KΩ~1MΩ)
DC0
~
20mA, 4
~
20mA
(external load resistor less than 500Ω)
Digital Input Range
12 bits binary
Distinguish Ratio
1/4095(12Bit); the convert data is stored in PLC in form of Hex. (12Bit)
Integral Precision
0.8%
Convert Speed
3ms/CH
Power Supply
DC24V±10%
,
100mA
4CH analogue output: voltage and current input selectable; Voltage input range is 0
~
5V,
0
~
10V selectable, current input range is 0
~
20mA, 4
~
20mA selectable;
10 bits high precision analogue output;
As the special module, 7pcs XC-E4DA can be connected to one XC series PLC main unit;
Brief Introduction
1
Terminal
Arrangement
3
Specification
2
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...