5 Input Specifications and Wiring Methods
XCC series
32
5
0
5
2
、
Input Terminals of HSC:
Each letter’s description:
U
Dir
A
B
Counter's pulse input
Counter's direction judgment
(OFF: increment counter, ON: decrement counter)
A phase input
B phase input
Normally, X0, X1 terminals’ input frequency can reach 80KHz under single-phase and AB phase
mode; the other terminal’s input frequency can reach 10KHz under single-phase mode and 5KHz
under AB phase mode. If X input terminals are not used as high speed input port, they can be used
as common input terminals. The detailed port assignment is shown below:
Note:
1.
XC2-16: C600, C602, C620, C630 max frequency is 10KHz;
2.
XC2-14: max frequency is 10 KHz.
XC2 series PLC
Increment Mode
Pulse + direction mode
AB phase mode
C600 C602 C604 C606 C608 C610 C612 C614 C616 C618 C620 C622 C624 C626 C628 C630 C632 C634
Highest
frequency
80K 80K 10K 10K 10K
80K 10K
80K 5K
4 times
frequency
√
Counter
interruption
√
√
√
√
√
√
√
X000
U
U
A
X001
U
Dir
B
X002
X003
U
U
A
X004
Dir
B
X005
X006
U
X007
U
X010
X011
X012
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...