Appendix special soft device list
3
、
O mapping
ID
Function
Initial value Description
FD8074
Y00
corresponds with
I**
0
Y0 corresponds with the number of
output image O**
FD8075
Y01
corresponds with
I**
1
Initial value are all decimal
FD8076
Y02
corresponds with
I**
2
……
……
FD8137
Y77
corresponds with
I**
63
4
、
I property
ID
function
Initial value
Description
FD8138
X00 property
all be 0
0: positive logic;
others: negative logic
FD8139
X01 property
FD8140
X02 property
……
……
FD8201
X77 property
5
、
power-off retentive area of soft components
Soft
component
FD
REGISTER
FUNCTION
Default
value
Power-off retentive
range
XC1
series
D
FD8202
Start tag of D power off
retentive area
100
D100~D149
M
FD8203
Start tag of M power off
retentive area
200
M200~M319
T
FD8204
Start tag of T power off
retentive area
640
-
C
FD8205
Start tag of C power off
retentive area
320
C320~C631
S
FD8206
Start tag of S power off
retentive area
512
-
XC2
series
D
FD8202
Start tag of D power off
retentive area
4000
D4000~D4999
M
FD8203
Start tag of M power off
retentive area
3000
M3000~M7999
T
FD8204
Start tag of T power off
retentive area
640
-
C
FD8205
Start tag of C power off
retentive area
320
C320~C639
S
FD8206
Start tag of S power off
retentive area
512
S512~S1023
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...