8 expansion devices
the data exchange quantity, expand the data memory space;
Items
Analogue Input (AD)
Temp. input
(
PT
)
Analogue output (DA)
Analogue Input
Current
0
~
20mA
4
~
20mA
PT100
-
Voltage
0
~
5V
0
~
10V
Temperature Range
-
-100~327
℃
-
Max input range
DC0
~
40mA
-
-
Analogue output
range
-
-
Current
0
~
10V
0
~
5V
Voltage
0
~
20mA
4
~
20mA
Digital input range
-
-
10 bits binary (0~1023)
Digital Output range
16 bits binary (0~65535)
-1000~3500
-
Distinguish Ratio
1/16383(16Bit)
0.01
℃
1/1023(10Bit)
PID Output value
0~K4095
-
Integral precision
0.8%
±0.01
℃
0.8%
Convert speed
20ms/CH
3ms/CH
Power supply
DC24V±10%, 100mA
PT0
COM
AI0
VI1
CI1
AI1
CI0
VI0
PT1
COM
VA
VB
24V
0V
VO0
VO1
CO1
IO0
CO0
IO1
Name
Terminals
Comments
Input terminals
PT0, PT1
Temperature
Input
Analogue
input,
PT100
temperature
sensor
(-100
℃
~
350
℃
)
VI0, VI1
Analogue Input
Voltage
Input
0~10V or 0~5V
Specification
2
Terminal Arrangement
3
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...