2 The Specifications and Parameters of CPU
Timer
points
640 points
T0~T99
:
100ms not accumulate
T100~T199
:
100ms accumulate
T200~T299
:
10ms not accumulate
T300~T399
:
10ms accumulate
T400~T499
:
1ms not accumulate
T500~T599
:
1ms accumulate
T600~T639
:
1ms precise time
Spec.
100ms timer: set time 0.1~3276.7sec.
10ms timer: set time 0.01~327.67sec.
1ms timer: set time 0.001~32.767sec.
Counter (C)
points
640
points
C0~C299: 16 bits sequential counter
C300~C598: 32 bits sequential/inverse counter
C600~C619: single phase high speed counter
C620~C629: dual-phase high speed counter
C630~C639
:
AB phase high speed counter
Spec.
16 bits counter: set value K0~32,767
32 bits counter: set value -2147483648~
+
2147483647
Data Register (D)
9024
words
D0~D3999
【
D4000~D4999
】
※
5
For Special Use
※
6
D8000~D9023
Flash ROM Register (FD)
8192
words
FD0~FD7167
For Special Use
※
6
FD8000~FD9023
Expand the internal
registers (ED)
※
7
36864
words
ED0~ED36863
High Speed Dispose
Ability
High speed counter, pulse output, external interruption
Password Protection
6 bits ASCII
Self-diagnose Function
Power on self-check
、
monitor the timer
、
grammar check
Items
Specifications
Program Executing Form
Loop scan form
Program Form
Instruction, Ladder
Dispose Speed
0.5 us
Power Off Retentive
Use Flash ROM and Li battery
User's program space
※
1
160KB
I/O points
Total I/O 24
32
60
XCM Series
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...