4 power supply specification and wiring method
4-1
.
Power Supply Specifications
The power supply specifications of XC series PLC are listed below:
※
1
:
Please use the wire cable thicker than 2mm
2
, to avoid the decrease of voltage;
※
2
:
Even happens the 10ms power off, the PLC can keep working. But when power off for long time or voltage
abnormal decrease, the PLC will stop working, output will be OFF. When power supply recover, the PLC
will RUN automatically.
※
3
:
The grounding terminals on basic units and expansions connect together and use the third type grounding.
1
AC Power Supply
Items
Content
Rated Voltage
AC100V~240V
Allow Voltage Range
AC90V~265V
Rated Frequency
50/60Hz
Allow momentary power off time Interruption Time
≤
0.5 AC cycle, interval
≥
1sec
Impulse Current
Below 40A 5mS/AC100V below 60A 5mS/AC200V
Maximum Power Consumption
12W
Power Supply for Sensor
24VDC
±
10% maximum 400mA
Items
Content
Rated Voltage
DC24V
Allow Voltage Range
DC21.6V~26.4V
Input Current (Only for basic
unit)
120mA DC24V
Allow momentary power off time 10mS
DC24V
Impulse Current
10A
DC26.4V
Maximum Power Consumption
12W
Power Supply for Sensor
24VDC
±
10% maximum 400mA
2
DC Power Supply Type
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...