Appendix special soft device list
value; if the temperature is higher than
, PID output the mini value;
Temperature difference δ
(unit: 0.1
℃
)
(sample temp Temperature difference δ)/10=display temperature value. Then
temperature display value can equal or close to the real temperature value. This
parameter has sign (negative or positive). Unit is 0.1
℃
, the default value is 0.
The set temperature
value(unit: 0.1
℃
)
Control system’s target temperature value. The range is 0
~
1000
℃
, the precision is
0.1
℃
.
Temperature control cycle
(unit: 0.1s)
Control cycle’s range is 0.5s
~
200s, the minimum precision is 0.1s. The write value is
the real temperature control cycle multiplies 10. i.e. 0.5s control cycle should write 5,
200s control cycle should write 2000.
Adjust environment
temperature value
(unit: 0.1
℃
)
If users think the environment temperature is different with the display temperature, he
can write in the known temperature value. At the moment of value written in, calculate
the temperature difference δ and save.
Calculate the temperature difference value δ=adjust environment temperature value
-
sample temperature value. Unit: 0.1
℃
.
E.g.: under heat balance status, user test the environmental temperature as 60.0
℃
with
mercurial thermometer, the display temperature is 55.0
℃
(correspond sample
temperature is 550), temperature difference δ=0. at this time, users write this
parameters with 600
,
temperature difference δ is re-calculated to be 50 (5
℃
), then the
display temperature = (sample temperature
+
temperature difference δ
)
/10 =60
℃
。
**Note: when users write the adjust temperature value, make sure that the temperature
is same with the environment temperature value. This value is very important, once
it’s wrong, temperature difference δ will be wrong, then effect the display temperature
Auto tune output value
The output when auto tune, use % as the unit, 100 represents 100% of full scale
output. 80 represent 80% of full scale output.
XC-E3AD4PT2DA
CH Nr.
AD
signal
PID output
value
PID run/stop bit
Set value
PID parameters:
Kp
、
Ki
、
Kd
、
control range
Diff
、
death range
Death
0CH
ID100
ID107
Y100
QD102
Kp------- QD109
Ki------- QD110
Kd------- QD111
Diff------ QD112
Death---- QD113
1CH
ID101
ID108
Y101
QD103
2CH
ID102
ID109
Y102
QD104
CH Nr.
PT
signal
PID output
value
PID run/stop bit
Set value
3CH
ID103
ID110
Y103
QD105
4CH
ID104
ID111
Y104
QD106
5CH
ID105
ID112
Y105
QD107
6CH
ID106
ID113
Y106
QD108
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...