8 expansion devices
8-3-1
.
XC-E8AD
0V
24V
AI0
C0
C1
C2
C3
AI3
AI2
AI1
.
.
VI0
VI1
VI2
VI3
C0
C1
C2
C3
CH
NAME SIGNAL
CH
NAME SIGNAL
CH0
AI0
VI0+ voltage input CH1 AI1
VI1+ voltage input
C0
VI0- voltage input
C1
VI1- voltage input
CH2
AI2
VI2+ voltage input CH3 AI3
VI3+ voltage input
C2
VI2- voltage input
C3
VI3- voltage input
Items
Voltage input (0CH-3CH) Current input (4CH-7CH)
Analog input bound DC0
~
5V, 0
~
10V
DC0
~
20mA, 4
~
20mA
Max input bound
±18V
0
~
40mA
Digital output bound
14 bits binary data
PID control value
0
~
K4095
Distinguish Ratio
1/16383
(
14Bit
)
Integrate Precision
0.8%
Convert speed
20ms/channel
Power used by analog
DC24V±10%, 100mA
14 bits high precision analog input
8 channels analog input
:
The first four channels voltage input (0~5V
、
0~10V two kinds)
;
The left 4 channels current input (0~20mA
、
4~20 mA
two kinds)
As special function module of XC, 7 models could be connected at most.
Support PID auto tune function
Brief Introduction
1
Specification
2
Terminal Arrangement
3
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...